Transformer full-load current calculator

Calculate primary and secondary current from transformer kVA and nominal voltages.

Inputs

Calculation steps

I₁ = 100000 / (√3 × 11000)

I₂ = 100000 / (√3 × 415)

Formula ID: TRANSFORMER_3PH_FULL_LOAD_V1

Assumptions and references

Nameplate apparent power is treated as available on both sides. This does not model losses, regulation, impedance, tap position or inrush.

UNDERSTAND THE TOOL

What this calculator does

Convert a transformer apparent-power rating into nominal full-load current on both sides for single-phase or balanced three-phase systems.

How to use it

  1. Choose the transformer phase arrangement.
  2. Enter the nameplate kVA rating.
  3. Enter primary and secondary nominal voltages.
  4. Review both current results and the excluded design checks.

Fields and meanings

Rating
Transformer apparent-power rating in kVA.
Primary voltage
Nominal supply-side voltage.
Secondary voltage
Nominal load-side voltage.
Phase
Select single phase or balanced three phase.
Review required. Inrush, impedance, regulation, losses, protection and fault levels require separate assessment.