Voltage drop and conductors
Three-Phase Voltage Drop Formula and Worked Example
A substituted example shows where √3, route length, resistance, reactance and power factor enter the result.
Open the voltage-drop calculator →Published 26 September 2026

The balanced three-phase formula
For a balanced three-phase AC load using line-to-line voltage and conductor impedance per kilometre:
ΔV = √3 × I × Lkm × (R cosφ + X sinφ).
I is line current in amperes; Lkm is the one-way route length in kilometres; R and X are the applicable resistance and reactance in Ω/km. The result is volts of line-to-line drop under the simplified steady-load model. If your source gives a circuit-specific mV/A/m coefficient instead, use its stated geometry and ΔV = (mV/A/m × I × Lm) / 1000; do not add another √3 factor unless that data source calls for it.
Open the R/X calculator with this example, then replace the illustrative values with traceable cable data for your circuit.
Define the case
Consider a balanced three-phase load with these preliminary inputs:
- line-to-line voltage: 415 V;
- line current: 20 A;
- power factor: 0.80;
- one-way route length: 50 m, or 0.05 km;
- resistance: 1.00 Ω/km;
- reactance: 0.08 Ω/km;
- one cable run per phase.
The conductor values are illustrative. A real calculation should use traceable data for the actual cable, temperature and arrangement.
Substitute the R/X formula
For balanced three phase:
ΔV = √3 × I × L × (R cosφ + X sinφ)
Power factor gives cosφ = 0.80, so:
sinφ = √(1 − 0.80²) = 0.60
Now substitute:
ΔV = 1.73205 × 20 × 0.05 × (1.00×0.80 + 0.08×0.60)
ΔV = 1.469 V
Percentage drop is:
1.469 / 415 × 100 = 0.354%
Estimated end voltage is approximately 415 − 1.469 = 413.53 V under the simplified steady-state assumptions.
Why reactance appears
In AC circuits, conductor impedance includes resistance and reactance. Their contributions to the in-phase voltage change depend on load power factor. Ignoring reactance may be acceptable for some preliminary short routes and conductor arrangements, but it should not be silently set to zero when traceable data says otherwise.
Route length and parallel runs
The 50 m is the physical source-to-load distance. The three-phase geometry is already represented by √3. Entering 100 m to represent an imagined return path would double the result incorrectly.
If two identical equal-sharing runs are used per phase, the simplified impedance contribution is divided by two once. Installation symmetry and current sharing must still be reviewed.
Compare with a chosen target carefully
A calculator can compare 0.354% with a target entered by the user. It cannot decide which target is legally or technically appropriate for every installation. Equipment starting, source variation and terminal voltage requirements may lead to a stricter project objective.
Finally, a small voltage-drop percentage does not establish cable suitability. Corrected ampacity, fault performance, protection and installation conditions remain independent checks.
With two equal parallel runs, the example’s ideal equivalent impedance is halved and the drop becomes about 0.735 V. Do not also divide the total entered load current: that applies sharing twice. The equal-sharing assumption requires matched routes and terminations.
Temperature and data provenance
Resistance rises with conductor temperature. If the 1.00 Ω/km figure is stated at 20°C but the conductor operates much warmer, using it unchanged may understate voltage drop. Prefer reviewed cable data at an appropriate temperature, or make a transparent temperature adjustment when the source basis supports it.
Reactance also depends on cable construction and arrangement. Do not transplant an R/X pair from a different product or geometry because the cross-sectional area looks similar. Record manufacturer, document, table, temperature and configuration beside the entered values.
Check motor-start and terminal needs separately
The steady 20 A calculation does not describe a motor start or another temporary high-current event. A circuit with a small running drop can experience a much larger transient drop. Equipment minimum terminal voltage and source impedance may govern the real design question.
Use this worked example to verify arithmetic and route geometry. For an actual circuit, pair the result with operating scenarios, corrected ampacity, fault-loop and protective-device checks, and the applicable project requirements.
Recalculate the example in R/X mode and retain the data source and temperature basis with the result.
Sources and limits
Preliminary engineering aid only. The example uses illustrative custom conductor data and a user-selected target; it is not a cable recommendation or code limit.
Verify applicable laws, standards, manufacturer data and project conditions with a qualified electrical professional before construction, procurement or regulatory submission.
CONTINUE READING
Related articles
Voltage drop and conductors
Voltage drop: route length, conductor data and useful checks
Voltage drop is easy to calculate badly. The important work is choosing matching conductor data, geometry and route length.
Voltage drop and conductors
Resistance, reactance and power factor in AC voltage drop
R and X do not contribute identically to the in-phase voltage change. Power factor sets the weighting in the common approximation.
Voltage drop and conductors
One-way route length versus total conductor length
Length errors often come from counting the return path twice. Start by identifying the geometry built into the selected formula or coefficient.
