Transformer terminal fault-current estimate

A narrow three-phase, transformer-only arithmetic shortcut—not a protection or equipment-selection result.

Inputs

Calculation steps

I_FL = 100000 VA / (√3 × 415 V) = 139.12 A; I_fault = 139.12 A / (5% / 100) = 2782.41 A

Formula ID: TRANSFORMER_3PH_TERMINAL_FAULT_INFINITE_SOURCE_V1

apparentPowerVA
100000
secondaryVoltageV
415
impedancePu
0.05
fullLoadCurrentA
139.12055
terminalFaultCurrentA
2782.4109

Intermediate values are retained without display rounding in the calculation.

Assumptions and references

Assumes a three-phase bolted fault at the low-voltage secondary terminals and an unlimited upstream source. The entered %Z must come from the actual transformer record. Source impedance, voltage variation, impedance tolerance, motors, downstream conductors and other fault types are excluded.

Understand percentage impedance →

UNDERSTAND THE TOOL

What this calculator does

Show how an entered transformer impedance changes a simplified symmetrical RMS fault-current estimate at the low-voltage secondary terminals.

How to use it

  1. Use the actual three-phase transformer nameplate kVA and impedance.
  2. Enter the low-voltage secondary line-to-line voltage.
  3. Review the full-load current and transformer-only terminal estimate.
  4. Obtain a complete project fault study before selecting any equipment.

Fields and meanings

Transformer rating
Three-phase apparent-power nameplate rating in kVA.
Secondary line voltage
Low-voltage line-to-line basis in volts.
Nameplate impedance
Actual transformer percentage impedance; no typical value is assumed.
Review required. Review required. This shortcut is not a complete available-fault-current, breaking-capacity, arc-flash or protection study.