Power-factor correction calculator

Estimate the preliminary reactive-power correction needed to reach a selected AC power factor.

Inputs

Calculation steps

Qᶜ = 100 × [tan(cos⁻¹ 0.8) − tan(cos⁻¹ 0.95)]

Current reduction: 27.46 A

Formula ID: POWER_FACTOR_CORRECTION_3PH_V1

Assumptions and references

Steady sinusoidal AC operation is assumed. The result does not specify capacitor stages, equipment, detuning or harmonic mitigation.

UNDERSTAND THE TOOL

What this calculator does

Compare reactive power before and after a selected power-factor target and show the resulting current change at the entered voltage.

How to use it

  1. Enter active power and the AC supply arrangement.
  2. Enter existing and target power factors.
  3. Confirm the target is not below the existing value.
  4. Treat the kVAr result as the starting point for a specialist study.

Fields and meanings

Active power
Operating electrical power in kW.
Existing PF
Measured or supportable present power factor.
Target PF
Selected design target, not an automatic requirement.
Voltage
Used to show the current before and after correction.
Review required. Do not select capacitor banks without reviewing harmonics, resonance, switching and equipment ratings.