Three-phase neutral current calculator

Estimate the fundamental neutral current from three phase-current magnitudes separated by 120°.

Inputs

Calculation steps

I_N = √(100² + 80² + 60² − 100×80 − 80×60 − 60×100)

Radicand: 1200.0000

Formula ID: NEUTRAL_CURRENT_120_DEG_V1

Assumptions and references

Sinusoidal fundamental phase currents are separated by 120°. Zero-sequence harmonics and waveform distortion are outside this calculation.

UNDERSTAND THE TOOL

What this calculator does

Vectorially add three fundamental phase-current magnitudes. Equal phase currents cancel; unequal currents leave a residual neutral current.

How to use it

  1. Enter the RMS fundamental current for L1, L2 and L3.
  2. Confirm the currents belong to the same operating condition.
  3. Review the calculated vector residual.
  4. Use measurement or harmonic analysis for nonlinear loads.

Fields and meanings

L1 current
Fundamental RMS current on phase L1.
L2 current
Fundamental RMS current on phase L2.
L3 current
Fundamental RMS current on phase L3.
Phase spread
A descriptive comparison, not a compliance limit.
Review required. Triplen harmonics add in the neutral and are not represented by this fundamental-only calculation.