Preliminary cable-size calculator
Evaluate custom cable data in ascending size order. Production automatic cable tables are intentionally not included.
Inputs
| Size | Corrected Iz | Voltage drop | Status |
|---|---|---|---|
| 2.5 mm² | 17.28 A | 4.2% | ampacity, voltage drop |
| 4 mm² | 23.04 A | 2.7% | ampacity |
| 6 mm² | 29.52 A | 1.8% | Pass |
| 10 mm² | 41.04 A | 1.1% | Pass |
Calculation steps
It = Ib / Ctotal = 25 / 0.720 = 34.72 A
Iz = Iz(table) × Ctotal. Formula ID: CABLE_SELECT_CUSTOM_V2
Assumptions and references
Preliminary calculation only. Verify inputs, manufacturer data, applicable standards, fault levels, and local requirements before construction or procurement.
UNDERSTAND THE TOOL
What this calculator does
Sort the cable candidates you supply and expose which preliminary checks each candidate passes or fails.
How to use it
- Enter design current and target drop.
- Supply traceable candidate and correction-factor data.
- Review corrected ampacity and voltage-drop outcomes.
- Independently verify the selected candidate before procurement.
Fields and meanings
- Design current
- Expected load current used for the comparison.
- Base ampacity
- A value from your own traceable dataset.
- Correction factors
- User-supplied multipliers for relevant conditions.
- Cable data
- Candidate size and any enabled voltage-drop or thermal information.
Review required. A passing custom-data result is not approval, certification or an installation instruction.