Preliminary cable-size calculator

Evaluate custom cable data in ascending size order. Production automatic cable tables are intentionally not included.

Inputs

SizeCorrected IzVoltage dropStatus
2.5 mm²17.28 A4.2%ampacity, voltage drop
4 mm²23.04 A2.7%ampacity
6 mm²29.52 A1.8%Pass
10 mm²41.04 A1.1%Pass
Calculation steps

It = Ib / Ctotal = 25 / 0.720 = 34.72 A

Iz = Iz(table) × Ctotal. Formula ID: CABLE_SELECT_CUSTOM_V2

Assumptions and references

Preliminary calculation only. Verify inputs, manufacturer data, applicable standards, fault levels, and local requirements before construction or procurement.

UNDERSTAND THE TOOL

What this calculator does

Sort the cable candidates you supply and expose which preliminary checks each candidate passes or fails.

How to use it

  1. Enter design current and target drop.
  2. Supply traceable candidate and correction-factor data.
  3. Review corrected ampacity and voltage-drop outcomes.
  4. Independently verify the selected candidate before procurement.

Fields and meanings

Design current
Expected load current used for the comparison.
Base ampacity
A value from your own traceable dataset.
Correction factors
User-supplied multipliers for relevant conditions.
Cable data
Candidate size and any enabled voltage-drop or thermal information.
Review required. A passing custom-data result is not approval, certification or an installation instruction.
Read the full explanation →